Page 38 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083
Piping Stub-up Within Cabinet
Unit End Compartment
Piping Stub-up Within 6" End Panel End Panel 6"
Application and Dimension
Wall Line
11 ½
10¾
Left End
of unit
(Less end panel)
Note: Space available in left end
compartment for piping stub-up.
Stub-up, including unions and shutoff
valves, must disconnect below oor
line for unit installation and removal.
1
Space available at left end of unit
for piping stub-up when 6" end
panel is used.
Left End of unit
(Less end panel)
Wall Line
4
1
Unit End Compartment
6
All dimensions in inches
Figure 71: Piping Stub-Up Details, 6" End Panel
End Panel Assembly
Accessory end panels are shipped separately with hardware and
kickplate.
The nal step of unit installation is attaching the end panels. End panels
are required unless the unit has adjoining matching cabinets.
1. Refer to Figure 72 for a 1" thick end panel. Attach two (2) Tinnerman
nuts to the top edge of the end panel and two (2) to the bottom
end of the unit. Align the end panel with the front and top edges
of the unit. Insert through upper mounting holes inside unit end
compartment and thread into tinnerman clips on the end panel.
Attach the end panel to the unit using four (4)
5/32" hex socket
head fasteners provided.
Figure 72: 1" End Panel
Figure 73: 6" End Panel with Provided Hardware
2. Refer to Figure 73 for 6" thick end panel.
a. Position bracket (YC1934) on wall so angle is 5" from
end of unit and near bottom.
b. Mark and drill required hole for device to fasten bracket
to wall (not included).
c. Attach the bracket to wall.
d. Attach two (2) Tinnerman nuts to the top edge of the end panel
and one (1) to the bottom front of the end frame.
e. Align the end panel with the front and top edges of the unit.
Attach end panel to the unit using three (3) 5/32
" hex socket
head fasteners provided. Bracket should prevent movement of
panel toward the unit when pressure is applied to the end panel.
Installing (Optional) End Panel
Tinnerman Nut,
Clip on End Panel
1"
End
Panel
1/4"- 20 × 1/2"
Screw
1/4"- 20 Tinnerman Nut, Clip
over Lower Hole in Unit Base
1/4"- 20 × 1/2" Screw
Steel Kickplate
21" Unit
Projection
Tinnerman Nut,
Clip on End Panel
6" End Panel
Oxford Brown Kickplate, Factory Assembled
to Base of End Panel
21" Unit
Projection
1/4"- 20 × 1/2" Screw & 1/4" Flat Washer
1/4"- 20 Tinnerman
Nut, Clip over Lower
Hole in Unit Corner
Bracket
Bracket
YC1934
5"
End of Unit
Angle Bracket
Welded for
Rigidity
5¼" Adapter Back Painted Top (Option)